SN-02 Specifications Sheets
230Volt Series
|
Model SN-02- |
1L |
2L |
3L |
5L |
7L |
10L |
15L |
20L |
25L |
30L |
40L |
50L |
60L |
75L |
100L |
|
|
Horse Power |
1 |
2 |
3 |
5 |
7.5 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
75 |
100 |
|
|
Output Current |
6 |
8 |
11 |
17.5 |
25 |
33 |
49 |
64 |
80 |
96 |
130 |
160 |
183 |
224 |
300 |
|
|
Enclosure |
NEMA 1 |
|||||||||||||||
|
POWER |
Input Voltage |
3 Phase 200/208/220 Vac (50/60 HZ); 230 Vac (60HZ) |
||||||||||||||
|
Output Frequency |
Up to 400 HZ standard; 1000 HZ by special order |
|||||||||||||||
|
Voltage Fluctuation |
10% |
|||||||||||||||
|
Frequency Fluctuation |
+/- 5% |
|||||||||||||||
|
Max Output Voltage |
3 Phase 200/208/220/230 Vac proportional to Input Voltage |
|||||||||||||||
|
CONTROL
|
Control Method |
Sine Wave PWM; 4 control methods: v/f; v/f with PG
feedback; |
||||||||||||||
|
Starting Torque |
150% at 1HZ |
|||||||||||||||
|
Speed Control Range |
1:100, 1:1000 with encoder feedback |
|||||||||||||||
|
Speed Control Accuracy |
+/- 0/2%; +/- 0.02% with encoder feedback |
|||||||||||||||
|
Frequency Control Range |
0.1 to 400HZ, to 1000HZ special order |
|||||||||||||||
|
Frequency Accuracy |
Digital Command: 0.01%; Analog Command: 0.1% |
|||||||||||||||
|
Frequency Resolution |
Digital Operator: 0.01 HZ; Analog Reference: 0.05 HZ/60HZ |
|||||||||||||||
|
Output Frequency Resolution |
0.01 HZ |
|||||||||||||||
|
Overload Capacity |
150% of drive rated output current for 1 minute |
|||||||||||||||
|
Frequency Set Signal |
DC: 0-10V (20K Ohm); -10 to +10V (20K ohm); 4-20mA (250 ohm) |
|||||||||||||||
|
Accel/Decel Time |
0.01 to 6000 seconds, set independently |
|||||||||||||||
|
Braking Torque |
Approximately 20% standard; up to 150% optional |
|||||||||||||||
|
Protective
|
Motor Overload Protection |
Protected by electronic thermal overload relay |
||||||||||||||
|
Instantaneous Overcurrent |
Motor coasts to stop at 200% of inverter rated current |
|||||||||||||||
|
Overload |
Motor coasts to stop after 1 minute of inverter rated output |
|||||||||||||||
|
Overvoltage |
Motor coasts to stop if DC bus exceeds 400Vdc |
|||||||||||||||
|
Undervoltage |
Motor coasts to a stop if DC bus drops to 200Vdc |
|||||||||||||||
| Momentary Power Loss |
Continuous operation during power loss less than 2 seconds (programmable) |
|||||||||||||||
|
Heatsink Overheat |
Protected by thermistor | |||||||||||||||
| Stall Prevention | During Accel, Decel & constant speed operation | |||||||||||||||
| Ground Fault | Protected by vector sum current detection electronically | |||||||||||||||
| Power Charge Indication | "CHARGE" LED remains on until bus voltage drops below 50Vdc | |||||||||||||||
|
Environment |
Ambient Temperature | -10oC to 40oC (NEMA 1 Type); -10oC to 45oC (Chassis Type) | ||||||||||||||
| Humidity | 90% Non-condensing | |||||||||||||||
| Storage Temperature | -20oC to 60oC | |||||||||||||||
| Location | Indoor (protected from corrosive and explosive gases and dust) | |||||||||||||||
| Vibration | 9.81m/s2 (1G) less than 20 HZ, up to 1.96m/s2 (.2G) at 20 to 50 HZ | |||||||||||||||
| Elevation | 1000m or less, derate above 1000m | |||||||||||||||
460 Volt Series
|
Model SN-02- |
1H |
2H |
3H |
5H |
7H |
10H |
15H |
20H |
25H |
30H |
40H |
50H |
60H |
75H |
100H |
150H | 200H | 250H | 300H | 400H | |
|
Horse Power |
1 |
2 |
3 |
5 |
7.5 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
75 |
100 |
150 | 200 | 250 | 300 | 400 | |
|
Output Current |
3.4 |
4.8 |
6.2 |
8.0 |
14 |
18 |
27 |
34 |
41 |
48 |
65 |
80 |
96 |
128 |
165 |
224 | 302 | 340 | 450 | 605 | |
|
Enclosure |
NEMA 1 |
||||||||||||||||||||
|
POWER |
Input Voltage |
3 Phase 380/400/440/460 Vac (50/60 HZ) |
|||||||||||||||||||
|
Output Frequency |
Up to 400 HZ standard; 1000 HZ by special order |
||||||||||||||||||||
|
Voltage Fluctuation |
10% |
||||||||||||||||||||
|
Frequency Fluctuation |
+/- 5% |
||||||||||||||||||||
|
Max Output Voltage |
3 Phase 380/400/440/460 Vac proportional to Input Voltage |
||||||||||||||||||||
|
CONTROL
|
Control Method |
Sine Wave PWM; 4 control methods: v/f; v/f with PG
feedback; |
|||||||||||||||||||
|
Starting Torque |
150% at 1HZ |
||||||||||||||||||||
|
Speed Control Range |
1:100, 1:1000 with encoder feedback |
||||||||||||||||||||
|
Speed Control Accuracy |
+/- 0/2%; +/- 0.02% with encoder feedback |
||||||||||||||||||||
|
Frequency Control Range |
0.1 to 400HZ, to 1000HZ special order |
||||||||||||||||||||
|
Frequency Accuracy |
Digital Command: 0.01%; Analog Command: 0.1% |
||||||||||||||||||||
|
Frequency Resolution |
Digital Operator: 0.01 HZ; Analog Reference: 0.05 HZ/60HZ |
||||||||||||||||||||
|
Output Frequency Resolution |
0.01 HZ |
||||||||||||||||||||
|
Overload Capacity |
150% of drive rated output current for 1 minute |
||||||||||||||||||||
|
Frequency Set Signal |
DC: 0-10V (20K Ohm); -10 to +10V (20K ohm); 4-20mA (250 ohm) |
||||||||||||||||||||
|
Accel/Decel Time |
0.01 to 6000 seconds, set independently |
||||||||||||||||||||
|
Braking Torque |
Approximately 20% standard; up to 150% optional |
||||||||||||||||||||
|
Protective
|
Motor Overload Protection |
Protected by electronic thermal overload relay |
|||||||||||||||||||
|
Instantaneous Overcurrent |
Motor coasts to stop at 200% of inverter rated current |
||||||||||||||||||||
|
Overload |
Motor coasts to stop after 1 minute of inverter rated output |
||||||||||||||||||||
|
Overvoltage |
Motor coasts to stop if DC bus exceeds 820Vdc |
||||||||||||||||||||
|
Undervoltage |
Motor coasts to a stop if DC bus drops to 380Vdc |
||||||||||||||||||||
| Momentary Power Loss |
Continuous operation during power loss less than 2 seconds (programmable) |
||||||||||||||||||||
|
Heatsink Overheat |
Protected by thermistor | ||||||||||||||||||||
| Stall Prevention | During Accel, Decel & constant speed operation | ||||||||||||||||||||
| Ground Fault | Protected by vector sum current detection electronically | ||||||||||||||||||||
| Power Charge Indication | "CHARGE" LED remains on until bus voltage drops below 50Vdc | ||||||||||||||||||||
|
Environment |
Ambient Temperature | -10oC to 40oC (NEMA 1 Type); -10oC to 45oC (Chassis Type) | |||||||||||||||||||
| Humidity | 90% Non-condensing | ||||||||||||||||||||
| Storage Temperature | -20oC to 60oC | ||||||||||||||||||||
| Location | Indoor (protected from corrosive and explosive gases and dust) | ||||||||||||||||||||
| Vibration | 9.81m/s2 (1G) less than 20 HZ, up to 1.96m/s2 (.2G) at 20 to 50 HZ | ||||||||||||||||||||
| Elevation | 1000m or less, derate above 1000m | ||||||||||||||||||||